The LWY on-site display turbine flow sensor is based on the LWGY basic turbine flow sensor, now battery-powered and equipped with an on-site display. This flowmeter is a new flow measurement instrument, integrating a sensor with display and computing functions, developed using advanced ultra-low-power single-chip microcomputer technology.
The LWY on-site display turbine flow sensor is based on the LWGY basic turbine flow sensor, now battery-powered and equipped with an on-site display. This flowmeter is a new flow measurement instrument, integrating a sensor with display and computing functions, developed using advanced ultra-low-power single-chip microcomputer technology. Compared to traditional turbine flow sensor and secondary instrumentation systems, it offers significant advantages, including compact size, light weight, intuitive and clear display, high reliability, immunity to external power supply influences, lightning resistance, and low overall cost. It can be widely used for liquid flow measurement in the petroleum, chemical, light industry, and food industries. This product offers superior performance, reaching the international advanced level of similar products.
For information on the flow measurement ranges of various flowmeter diameters, sensor dimensions, installation instructions, and maintenance, please refer to Section 2 of this manual, "LWGY Basic Turbine Flow Sensor."
Left: Confirm parameter settings and exit submenu;
Down: Factory settings shortcut, downshift, and decrement;
Up: Decrement;
Right: Enter parameter settings.
Converter Parameter Description Instantaneous Flow Parameter Settings
Flow Units |
Options: L/s L/m L/h m3/s m3/m m3/h Nm3/h USG/s USG/m USG/h Kg/s Kg/m Kg/h t/s t/m t/h |
How many decimal places are in the flow rate? |
Options: 0 1 2 3 Default value: 1 |
Range |
Floating point number: 99999999.00-0.00 m³/h, default value: 100.0 m³/h |
Small Signal Cutoff |
Floating Point: 9.90 to 0.00%, Default: 0.0% |
High Alarm |
Floating Point: 99.00 to 1.00%, Default: 90.0% |
Low Alarm |
Floating point number: 99.00 to 0.00%, default value: 0.0% |
Damping time |
Floating point number: 30.0 to 0.1, default value: 1 |
Total amount settings: Define parameters related to the total amount.
Quantity unit |
Options: L(liter) m² Nm³ USG Kg t(ton) , |
Quantity decimal places |
Options: 0 1 2 3 Default value: 1 |
Preset total amount |
Options: 99999999.00-0.00 m³/h, default: 0.0 m³/h |