RP62 is equipped with a microprocessor that can measure multiple pressures, and supports multiple outputs and multiple parameter settings, and can realize HART ® communication functions and other operations. It can be used for pressure measurement, flow measurement, and liquid level measurement.
1. Multiple inputs: differential pressure (DP), gauge pressure (GP), absolute pressure (AP)
2. Multiple outputs: 4 ~20mA (analog), digital signal output
3. Automatic compensation for ambient temperature
4. Various parameter settings:zero/volume conversion, fault alarm, unit conversion, fine-tuning, etc.
5. Digital communication: HART communication instructions
6. Explosion-proof appearance: CSA, FM, ATEX, GOST
7. Optimal performance: high accuracy: ±0.075% of span (±0.04% of span), stability: ±0.01% / year, high range ratio: 100:1
8. Flexibility: Setting parameters through HART ® protocol instructions, zero point adjustment
9. Reliability: MTBF 20 years; continuous self-detection function (sensor, memory, communication); automatic compensation function (ambient temperature compensation, sensor input linearization); software and hardware fault alarm function; configuration protection: EEPROM write protection function; CE EMC standard (EN50081-2, EN50082-2)
| Process interface materials | Process isolation diaphragm: 316L SS, Hastelloy C-276, Monel, Tantalum |
| Process interface: 316SS, carbon steel (galvanized), Hastelloy, Monel | |
| O-ring: Teflon, fluorinated rubber | |
| Exhaust/drain valve: 316L SS, Hastelloy C-276 | |
| Bolt: carbon steel, A286 SS (NACE) | |
| Note: There are other special anti-corrosion materials available for the liquid-contacting parts to meet various working conditions. Please contact VIRVO ® Company | |
| Mounting bracket | Carbon steel (galvanized) or stainless steel angle bracket, carbon steel flat bracket |
| Filling fluid | Silicone oil DC200 or CTFE (fluorine oil) |
| Case | Epoxy polyester paint, low copper aluminum alloy. Meet NEMA 4X (waterproof) and NEMA 7 (explosion-proof) requirements, optional stainless steel material |
| Process connection | 1/4NPT, 1/2NPT conversion connector (optional) |
| Wiring | 16AWG (1.5mm diameter) |
| Net weight | 4.2kg, about 5kg with accessories |
| Packing size | 234X185X155mm |
| Nameplate | 304 stainless steel |
| Hazardous area certification | With explosion-proof and intrinsic safety certification, it can be used in ClassⅠ, Devision 1, GroupA, B, C, D occasions, and non-flammable ClassⅠ, |
| Devision 2, GroupA, B, C, D occasions. ATEX standard EEx ia ⅡCT4, T5, T6 and EExd ⅡCT5, T6 certification |
| Power supply voltage | 11.9~45 VDC | Output signal | 4~20mA DC/HART |
| HART load resistance | 250~1500Ω | Insulation voltage | 500 Vrms (707VDC) |
| Damping time | 0.25S | Startup time | 5S |
| Accuracy | ± 0.075% of Span |
| (0.2URL≤Span≤URL) | |
| ±[0.05+0.005x(URL/Span)]% | |
| of Span(0.05URL≤Span<0.2URL) | |
| Stability | ±0.01% full scale/year |
| Temperature effect | ±[0.025%URL+0.125% Span]/28 |
| Vibration effect | The frequency is 200Hz on any axis, and the error caused is ±0.05%/g of the range |
| Influence of power supply voltage | 0.005% full scale/volt |
| CE certification | 89/336/EEC, electromagnetic compatibility (EMC) standard |
| Parameters | Rated environment | Operation Limits | Transportation and Storage |
| Ambient Temperature (℃) |
-40~85 |
-40~91 |
-55~125 |
| Body Temperature (℃) |
-40~110 |
-40~125 |
-55~125 |
| Humidity (%RH) | 10~85 | 0~100 | 0~100 |
| Overpressure capability | 14MPa, special up to 21MPa | ||
| Vacuum degree (KPa) | 0 | 3.5 | -- |